Victron Energy smallBMS

£41.16

SKU: BMS400100000 Categories: ,

Description

 

Features of the smallBMS

Load Disconnect output
The Load output is normally high and becomes free floating in case of cell under voltage (default 2,8V/cell, adjustable on the battery between 2,6V and 2,8V per cell). Maximum current: 1A. The Load output is not short-circuit protected.

The Load output can be used to control:
– A high current relay or contactor.
– The remote on/off input of a Battery Protect, inverter or DC-DC converter or other loads (a non-inverting or inverting on/off cable may be required).

 

Pre-alarm output
The smallBMS has a pre-alarm output is normally free floating and becomes high in case of imminent cell under voltage (default 3,1V/cell, adjustable on the battery between 2,85V and 3,15V per cell). Maximum current: 1A (not short circuit protected).
The minimum delay between pre-alarm and load disconnect is 30 seconds.

 

Charge disconnect output
The Charger output is normally high and becomes free floating in case of imminent cell over voltage or over temperature. Maximum current: 10mA.
The Charger output is not suitable to power an inductive load such as a relay coil.

The Charger output can be used to control:
– The remote on/off of a charger
– A?Cyrix-Li-Charge?relay
– A?Cyrix-Li-ct?Battery Combiner

 

System on/off input

The system on/off input controls both outputs. When off, both outputs will be free floating so that loads and chargers are turned off.
The System on/off consists of two terminals: Remote L and Remote H.
A remote on/off switch or relay contact can be connected between L and H.
Alternatively, terminal H can be switched to battery plus, or terminal L can be switched to battery minus.

 

smallBMS protects 12V, 24V and 48V systems

Operating voltage range: 8 to 70V DC